Technical Data - Disconnector/Isolators
Horizontal Double Break Disconnector/Isolators
| Sl.No | Technical Particulars | Unit | Rated Values | ||||
|---|---|---|---|---|---|---|---|
| 36 kV | 72.5 kV | 123 kV | 145 kV | 245 kV | |||
| I | Rated voltage | [kV] | 36 | 72.5 | 123 | 145 | 245 |
| II | Rated frequency | [Hz] | 50 | 50 | 50 | 50 | 50 |
| III | Rated current | [Amps] | 3150 | 3150 | 3150 | 3150 | 3150 |
| IV | Rated short circuit withstand value | [kA] | 31.5 | 40 | 40 | 40 | 50 |
| V | Rated short circuit duration | Sec. | 3 | 3 | 3 | 3 | 3 |
| VI | Rated PF withstand voltage across isolating distance | [kVr] | 80 | 160 | 265 | 315 | 530 |
| VII | Rated PF withstand voltage between live terminals and ground | [kVrms] | 70 | 140 | 230 | 275 | 460 |
| VIII | Lightning Impulse withstand across Isolating distance | [kVp] | 195 | 375 | 630 | 750 | 1200 |
| IX | Lightning Impulse withstand between live terminals and ground | [kVp] | 170 | 325 | 550 | 650 | 1050 |
| X | Switching Impulse withstand across Isolating distance | [kVp] | - | - | - | - | - |
| XI | Switching Impulse withstand across between live terminals and ground | [kVp] | - | - | - | - | - |
Horizontal Centre Break Disconnector/Isolator
| Sl.No | Technical Particulars | Unit | Rated Values | ||||
|---|---|---|---|---|---|---|---|
| 36 kV | 72.5 kV | 123 kV | 145 kV | 245 kV | |||
| I | Rated voltage | [kV] | 36 | 72.5 | 123 | 145 | 245 |
| II | Rated frequency | [Hz] | 50 | 50 | 50 | 50 | 50 |
| III | Rated current | [Amps] | 3150 | 3150 | 3150 | 3150 | 3150 |
| IV | Rated short circuit withstand value | [kA] | 31.5 | 40 | 40 | 40 | 50 |
| V | Rated short circuit duration | Sec. | 3 | 3 | 3 | 3 | 3 |
| VI | Rated PF withstand voltage across isolating distance | [kVrms] | 80 | 160 | 265 | 315 | 530 |
| VII | Rated PF withstand voltage between live terminals and ground | [kVrms] | 70 | 140 | 230 | 275 | 460 |
| VIII | Lightning Impulse withstand across Isolating distance | [kVp] | 195 | 375 | 630 | 750 | 1200 |
| IX | Lightning Impulse withstand between live terminals and ground | [kVp] | 170 | 325 | 550 | 650 | 1050 |
| X | Switching Impulse withstand across Isolating distance | [kVp] | - | - | - | - | - |
| XI | Switching Impulse withstand across between live terminals and ground | [kVp] | - | - | - | - | - |